API has generated the standard API Effective Orifice Area with corresponding designation letter (following table). Besides, standard effective orifice area, it also has a series of corresponding inlet size, outlet size combination for various pressure classes of flanged relief valves. All these information are tabulated in API Std 526 Flanged Steel Pressure Relief Valves.
API Relief Valve Standard Effective Discharge Orifice Areas | ||
Designation | in2 | cm2 |
D | 0.110 | 0.71 |
E | 0.196 | 1.26 |
F | 0.307 | 1.98 |
G | 0.503 | 3.24 |
H | 0.785 | 5.06 |
J | 1.287 | 8.30 |
K | 1.838 | 11.85 |
L | 2.853 | 18.40 |
M | 3.600 | 23.23 |
N | 4.340 | 28.00 |
P | 6.380 | 41.16 |
Q | 11.050 | 71.29 |
R | 16.000 | 103.22 |
T | 26.000 | 167.74 |
One shall remember above effective areas are valid only when used with the sizing equations contained in API RP 520 Part I - Sizing, Selection & Installation of Pressure-Relieving Devices in Refinery.
Related Articles
- What is Capacity Correction Factor (CCF) due to Back pressure for PSV ?
- PSV Constant Back Pressure Correction Factor (Kb) for Vapor & Gas
- Several Impact of Backpressure on Conventional PRV
- How Back Pressure Affect Conventional PSV Set Pressure Subject to It Vent
- Back Pressure Affect Conventional PSV Set Pressure : Case Study #1 - Bonnect Vent to ATM
- Back Pressure Affect Conventional PSV Set Pressure : Case Study #2 - Non-Bonnect Vent